Chapter 4: Programming
Use Start Time:
Checking this box will make the CPP Monitor 2000 start its Data
Logger at the time indicated in the Start Time box. If this box is not
checked, Datalogging will begin immediately.
Start Time:
CPP Monitor 2000 can be programmed to begin Datalogging at a
particular time of day. When CPP Monitor 2000s internal clock
reaches the programmed Start Time, the unit will begin Datalogging
the selected input values at the programmed interval. The Start
Time function is used to delay the start of Datalogging. Once
Datalogging has begun, the Start Time programming is ignored.
Default Setting: 12:00:00AM
Inputs Being Logged:
This selects which inputs CPP Monitor 2000 will log. The units data
logger can store 32,768 samples. Every time the unit logs input
data, it uses one sample for each checked box. For example, if
inputs 1-5 are selected, 5 samples are used up every time CPP
Monitor 2000 logs data. The more inputs you select, the fewer
samples are left available. Below is a table showing the number of
Data Samples available vs. the number of Inputs Being Logged.
Once the CPP Monitor 2000 has filled its Data Logger, it will begin
overwriting the oldest Data Log samples with new ones.
# of Inputs Being Logged Data Samples Available
1 32,768
2 16,384
3 10,922
4 8,192
5 6,553
6 5,461
7 4,681
8 4,096
9 3,640
10 3,276
Start/Stop datalogging:
To start Datalogging, click on this button.
Default setting: Stopped
NOTE: Any changes to the Data Log Programming
form will RESET the datalogger.